Leroy-Somer Alternator AVR R450 Excitation System
1.1
- Description
The R450 AVR is supplied
in a casing designed to be mounted on a panel with dampers.
- Operating temperature:
- 30°C to + 65°C.
- Storage temperature: -
55°C to + 85°C.
- Shocks on the base: 9
g depending on the 3 axes.
- Vibrations: less than
10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g.
The AVR is IP00, it must
be incorporated in an environment which ensures it a IP20 protection.
1.2
- Characteristic
The connection is
realised by “Faston” connectors and the voltage sensing is single - phase.
2
- POWER SUPPLY
Both the SHUNT/AREP
& PMG excitation systems are controlled by the AVR.
2.1
- AREP excitation system
With AREP excitation,
the electronic AVR is powered by two auxiliary windings which are independent
of the voltage sensing circuit.
The first winding has a
voltage proportional to the alternator main voltage (Shunt characteristic), the
second one has a voltage proportional to the stator current (compound
characteristic : Booster effect).
The power supply voltage
is rectified and filtered before being used by the AVR monitoring transistor.
This system provides the
machine with a short-circuit current capacity of 3 IN for 10 s. The rotating
switch should be in the AREP position (see 3.2.3).
2.2
- PMG excitation system
With PMG excitation, a
permanent magnet generator (PMG) added to the alternator supplies the AVR with
voltage which is independent of the main alternator winding.
This system provides the
machine with a short-circuit current capacity of 3 IN for 10 s.
The AVR monitors the
alternator output voltage by adjusting the excitation current. The rotating
switch should be in the PMG position (see 3.2.3).
2.3
- SHUNT or separate excitation system
With SHUNT excitation,
the AVR is powered by the main winding (100V to 140V -50/60 Hz ) by using X1,
X2 on the AVR. The rotating switch should be in the SHUNT/ AREP position (see
3.2.3).
3 - TECHNICAL
CHARACTERISTICS
3.1 - Electrical
characteristics
- maximum power supply:
150V - 50/60 Hz
- Rated overload
current: 10 A - 10 s
- Electronic protection:
- In the case of a
short-circuit, the excitation current is reduced to a value less than 1A after
10 s
- In the event of loss
of voltage reference, the excitation current is reduced to a value less than 1A
after 1s for AREP/SHUNT, 10 s for PMG.
- In the event of
overexcitation, the current is reduced as indicated in the next diagram (see
3.2.1.4).
- Fuses: F1 on X1 and F2
on Z2 10A, 250V.
- Voltage sensing
• 0-110 V terminals = 95 to 140
V
• 0-220 V terminals = 170 to 260 V
• 0-380 V terminals = 340 to 528 V
For other voltages, a
transformer should be used.
- Voltage regulation:±
0.5%.
- Current sensing:
(parallel operation): input S1, S2 intended for 1 C.T. < 2.5 VA cl1,
secondary 1 A or 5 A.