Excitation Limitation of Leroy-Somer Alternator AVR
3.2.1.4
Excitation Limitation
The limitation threshold
must be adjustable between 1 and 5.5 A. The genset breaker must be open during
the short circuit. If the genset is restarted in short circuit, there is a
excitation build up during 10s again at the maximum value.
Operation between 3 and
6 In when short-circuited:
The excitation current
ceiling during a short-circuit equals 2.9 times the fixed threshold when
setting the permitted excitation ceiling in continuous operation.
When the threshold is
exceeded for a period = 10 s the current is reduced to a value between 0.5 and
0.7 A (shutdown).
In all operating
conditions the maximum excitation current must be limited to 9 A ± 0.5 A.
Overrun indications:
One green LED:
- Lights up when the
excitation current is below the continuous operation threshold It signals the
AVR normal operation.
- Turns off when the
excitation current ceiling used to obtain short-circuit operation is reached
and when the excitation current is reduced to the shutdown value.
- Flashes when the over
excitation counter is decrementing.
NB: After an obvious
short-circuit, the voltage is limited to 70% of the rated voltage. This avoids
overvoltages on machines whose no-load excitation current is below the “lower
current” threshold (only in AREP).
Leroy-Somer alternator
excitation current
One red LED:
- Lights up
simultaneously with the green led when the continuous operation threshold is
reached for more than 90 s and the excitation current is reduced to the
continuous operation threshold. It is used to set the excitation current
ceiling
- Turns off when the
excitation current is less than the setting value (< 110% In)
- Flashes when the
excitation current is above the continuous operation threshold during less than
90 s.
Green LED stays on,
- flashes when the
excitation current has reached the ceiling in < 10s with PMG excitation.
- ftays on if Iexc = I
Shutdown.
WARNING: If the overload
protection is activated, a voltage drop possibly exceeding 10% of the reference
voltage will be observed.
The AVR does not provide
undervoltage protection. The customer will need to make sure that their
installation is correctly protected against undervoltages.
During load shedding, an
overvoltage is observed, which will disappear in a few seconds.
3.2.2
- Rotating switch selection: LAM and U/F
- Pos 0: Change in the
voltage according to the U/F ratio, knee-point position at 48 Hz.
- Pos 1: Change in the
voltage according to the 2U/F, knee-point position at 48 Hz.
- Pos 2: Change in the
voltage according to the self auto-adaptating LAM combined with 2U/F,
knee-point position at 48 Hz.
- Pos 3: Change in the
voltage according to the U/F ratio, knee-point position at 58 Hz
- Pos 4: Change in the
voltage according to the 2U/F, knee-point position at 58 Hz.
- Pos 5: Change in the
voltage according to the self auto-adaptating LAM combined with 2U/F, knee-point
position at 58 Hz.
- Pos 6: Change in the
voltage according to the U/F ratio, knee-point position at 65 Hz (Tractelec
application and variable speed above 1800 rpm).
- Pos 7: Special (not
used).
- Pos 8: Change in the
voltage according to the U/F ratio, knee-point position at 48 Hz or 58 Hz
according to selection of the frequency by an external contact.
- Pos 9: Change in the
voltage according to LAM 1, knee-point position at 48 Hz or 58 Hz according to
selection of the frequency by an external contact
WARNING: For Pavers and
hydraulic applications, select positions 0 (50 Hz) or 3 (60 Hz).
3.2.3
- Rotating switch: excitation type and time response
0: AREP excitation and
normal time response.
3: AREP excitation and
fast time response.
1: PMG excitation and
normal time response.
2: PMG excitation and
fast time response.
For SHUNT applications, AREP excitation must be selected.
3.2.4 - Rotating switch:
voltage sensing
Phase sensing
0: Single phase sensing
- LSA46 / 47 series.
3: Single phase sensing
- LSA49 / 50 series.
1: Three-phase sensing
with optional module R731
- LSA46 / 47 series.
2: Three-phase sensing
with optional module R731
- LSA49 / 50 series.
3.3
- U/F and LAM function
3.3.1 - Frequency
variation compared with voltage (without LAM)
3.3.2 - LAM (Load
Acceptance Module) characteristics
3.3.2.1 - Voltage drop
The LAM system is
integrated in the AVR. As standard it is active.
Role of the LAM:
On application of a
load, the genset rotation speed decreases. When it falls below the preset
frequency threshold, the LAM causes the voltage to drop proportionately to the
frequency (LAM1) or to the active power (LAM2) depending the the rotating
switch position. This reduces the active load scale applied until the speed
returns to its rated value.
Hence the LAM can be
used either to reduce the speed variation (frequency) and its duration for a
given applied load, or to increase the applied load possible for one speed
variation (turbo-charged engine).
To avoid voltage
oscillations, the trip threshold for the LAM function should be set
approximately 2 Hz below the rated frequency.
3.3.2.2
- Soft voltage recovery function
During load impacts, the
function helps the genset to return to its rated speed faster with a gradual
increase in voltage according to the principle:
- If the speed drops
between 46 and 50 Hz (in 50Hz operation), the rated voltage is recovered by
following a fast gradient.
- If the speed drops
below 46 Hz, since the engine needs more help, the voltage follows a slow
gradient as it returns to the reference value.
Comments